Product Category
I/P Transducers
Share to:
Description: The aira 500 IP series transducers are ideally used to convert current or voltage input signal to a linearly proportional pneumatic output pressure. This versatile instrument is a rugged and reliable force balance transducer for use in both process control and industrial applications, for standard process control applications which typically utilize 3 to 15 psig output, and industrial & high-pressure applications which typically utilize pressure output up to 120 psig. Aira 500 IP series transducers combine low cost, high accuracy, and minimum air consumption with field-proven technology. Versatile design features and rugged, compact housing with a choice of CMRI and ATEX* approved versions for explosion-proof or intrinsically safe operation when used with a suitable barrier. Principle of Operation The aira 500 IP series transducer is a balance device in which, when electrical current is passed through the coil of the transducer, a magnetic field is created which acts on the magnet assembly, causing the anvil & diaphragm to move away from or forward the nozzle (flapper nozzle) depending on the direction of current flow. Motion at the nozzle assembly is proportional to the amount of current passing through the coil. The flapper/and move away from or forward towards the nozzle creates back pressure which acts as pilot pressure to an integral booster relay. When input electrical current increases (or decreases for reverse acting) proportional output pressure increases. Zero and Span are calibrated by turning the easily accessible adjusting screw on the front face of the unit. The zero-adjusting screw causes the nozzle e to move relative to the flapper/anvil. The span adjusting screw is a potentiometer that limits the current through the coil. A thermistor circuit in series with the coil provides temperature compensation Split Ranging If split ranging id is required the 4-20 mA input and 3-15 psig output version (aira IP-501) can be recalibrated to provide 3-9 psig or 9-15 psig output. Mounting The aira 500IP series transducers can be pipe, panel, or bracket mounted in any position. Positions other than vertical will require recalibration of the zero and span adjustment. Transducers should be mounted in a vibration-free area. Field Reversible All aira 500IP series transducers are calibrated at the factory for direct-acting operation but may be used in reverse-acting mode by reversing the polarity of signal leads and recalibrating. When calibrated for reverse-acting applications it provides a minimum of their full rated output pressure (i.e. 3 psig) upon input signal failure
Integrated Characteristics
- Compact Design.
- Low Air Consumption.
- Integral Volume Booster flow capacity up to 20 SCFM is boosted by the built-in volume booster.
- Field Reversible Output is inversely proportional to the input signal.
- Flexible Adjustments of Zero & Span.
- Standard Process Inputs.
- Split Ranging.
- NEMA4X (IP65) Enclosure Optional.
- Saving in Investments.
- CMRI and ATEX approval pending.
Applications
- The aira 500 IP series transducers convert electrical signal to a pneumatic output which can be used to operate the following:
- Valve, Valve-Actuators
- Damper and Louver Actuators
- Valve Positioners
- Air-Cylinders
- Relays
- Clutches
- Web Tensioners and Brakes
Used in:
- Petrochemical Processing Systems
- Energy Management
- HVAC Systems
- Textile Processing Systems
- Pharmaceutical Processing System
- Pulp and Handling Controls
| Specifications | Low Output Range (up to 30 psig) | High Output Range (up to 120 psig) |
| Supply Pressure Range (Min./Max.) | Minimum - 21 kPa(3psig) above maximum output Maximum - 700 kPa (100 psig) | Minimum = 35 kph (5psig) above maximum output Maximum - 1050 kPa (150 psig) |
| Supply Pressure Sensitivity | ± 0.15% of span per 10kpa (± 0.1 % of span per psig at mid range) | ± .005% of span per 7.0 kpa (1.0 psig) |
| Terminal Based | ± 1.0% of Span | ± 1.5% of span typical ± 2.0%max. |
| Linearity | ± 0.5% of span | ± 1.0% of span |
| Repeatability | ± 1.0% of Span | ± 1.0% of span |
| Hysteresis Response Time | Depends on the pressure range type. less than 0.25 sec. for 3-15 psig units | Depends on the pressure range - type. |
| Flow Rate | 7.6m3/hr(4.5 SCFM) at *175kpa(25psig) supply 20.0m3/hr (12.0 SCFM) at 700 kpa (100 psig) supply | 40.8m3/hr(24.0 SCFM) at 1050 pa (150 psig) supply |
| Relief Capacity | 3.4 m3/hr(2SCFM) at 35 kph (5psig)above 140 kph (20 psig) set point | 11.9m3/hr(7SCFM) at 35kpa (10psig) above 140 kph (20 psig) set point |
| Maximum Air Consumption Media | 0.3m3/hr(0.15 SCFM) at midrange typical Oil-free, clean dry air filtered to 40 microns. | 0.15 m3/hr (0.08 SCFM) at midrange typ. |
| Temp. Range (Operating) | -30°C to 60°C(-20°F to 140°F) | |
| Port Sizes | 1/4" NPT (Pneumatic) DIN 43650 connector (Electric) | 1/4" NPT (Pneumatic) DIN-43650 connector (Electric) |
| Weight | 2.2 Ibs. (1.0kg) approx. | 2.2 lbs.(1.0kg) approx |
Specifications:
| IP 501 | I/P Transducers 500IP | |||
| Output Range | ||||
| Part No. | Input | psi | kpa | lmpedance±1% |
| IP 501 | 4-20 mADC | 3-15 | 20-100 | 200Ώ |
| IP 502 | 4-20 mADC | 9-15 | 60-100 | 110Ώ |
| IP 503 | 4-20 mADC | 3-9 | 20-60 | 110Ώ |
| IP 504 | 4-20 mADC | 3-27 | 20-185 | 240Ώ |
| IP 505 | 4-20 mADC | 6-30 | 40-200 | 240Ώ |
| IP 506 | 4-20 mADC | 1-17 | 7-117 | 270Ώ |
| IP 507 | 10-50 mADC | 3-15 | 20-100 | 90Ώ |
| IP 508 | 10-50 mADC | 3-27 | 20-185 | 105Ώ |
| IP 509 | 10-50 mADC | 6-30 | 40-200 | 105Ώ |
| IP 510 | 4-20 mADC | 2-60* | 14-420 | 245Ώ |
| IP 511 | 3-120* | 20-830 | 280Ώ | |
| IP 512 | 0-60 mADC | 2-120* | 15-830 | 240Ώ |
| E/P Transducers 500 IP | ||||
| IP 513 | 0-5VDC | 3-15 | 20-100 | 625Ώ |
| IP 514 | 0-5VDC | 3-17 | 20-185 | 550Ώ |
| IP 515 | 0-5VDC | 6-30 | 40-200 | 560Ώ |
| IP 516 | 1 -9VDC | 3-15 | 20-100 | 1010Ώ |
| IP 517 | 1 -9VDC | 3-27 | 20-185 | 860Ώ |
| IP 518 | 1 -9VDC | 6-30 | 40-200 | 860Ώ |
| IP 519 | 0-5VDC | 2-60* | 14-120 | 520Ώ |
| IP 520 | 0-10VDC | 3-120* | 20-830 | 825Ώ |
Output shows are as calibrated at the factory. Large span adjustment capability allows recalibration to achieve output ranges from 20-240 kpa (3-35 psig) to 20-1000kpa (3-145 psig) Approved Pending